The MAXX Compact Exhaust Fan line is a complete solution for air renewal in various environments with little or no ventilation. With different models designed to meet specific requirements, the MAXX line provides comfort and air quality for occupants.
Practicality: Ensures maximum operational efficiency without complex assembly/disassembly requirements during preventive or corrective maintenance.
Easy Maintenance: The ability to remove the motor housing without dismantling the entire installation makes maintenance faster and more convenient, saving time and reducing the inconvenience of extensive disassembly. If the motor needs to be replaced, the process is also simplified, eliminating the need to modify the ductwork.
Installation in Limited Spaces: The compact design of MAXX exhaust fans allows installation in locations with limited available space, making them ideal for environments with space constraints.
Product Overview

Application and Focus
- Application: Ideal for boosting airflow in long duct runs, ensuring a constant and powerful airflow. Its external air intake capability makes it a versatile solution for various needs and also an excellent booster for filter hoods, optimizing exhaust performance and keeping the environment free from odors and impurities.
- Focus: High pressure and high airflow for large environments.
Key Features
- Duct Design: Optimized design to maximize airflow in duct systems.
- Compact Design: Ideal for installations in limited spaces.
- Durable Motor: Equipped with ball bearings for extended service life.
- Flexible Installation: Can be installed in series or in parallel.
- Enhanced Safety: IP X4 protection rating and Class II insulation.
- Thermal Protector: Prevents motor overheating.
- Airflow Control: Two adjustable speeds.
- Easy Maintenance: Full access to the motor without the need to disconnect the duct.
- Certifications and Standards: Compliant with INMETRO Ordinance 371/2009 and ETL certified for the USA and Canada (models 100 to 200 / 115V).
- Appearance: White color.
- Warranty: 1 year.
Technical Specifications
| MAXX | MODEL | |||||||
|---|---|---|---|---|---|---|---|---|
| Frequency | 50 Hz | 100 | 125 | 150 | 200 | 250 | 315 | |
| Maximum Airflow | m³/h | Min | 152 | 204 | 325 | 608 | 963 | 1548 |
| Máx | 207 | 287 | 460 | 867 | 1171 | 1958 | ||
| CFM | Min | 89 | 120 | 191 | 358 | 567 | 911 | |
| Máx | 122 | 169 | 271 | 510 | 689 | 1152 | ||
| Maximum Pressure | mmWG | Min | 13 | 12 | 11 | 14 | 23 | 30 |
| Min | 24,3 | 25 | 22 | 28 | 34 | 49 | ||
| In. W.G | Min | 0,512″ | 0,472″ | 0,433″ | 0,551″ | 0,906″ | 1,181″ | |
| Máx | 0,957″ | 0,984″ | 0,866″ | 1,102″ | 1,339″ | 1,929″ | ||
| Frequency | 60 Hz | 100 | 125 | 150 | 200 | 250 | 315 | |
| Maximum Airflow | m³/h | Min | 189 | 285 | 467 | 830 | 1064 | 1650 |
| Máx | 248 | 345 | 552 | 1040 | 1405 | 2350 | ||
| CFM | Min | 111 | 168 | 275 | 488 | 626 | 971 | |
| Máx | 146 | 203 | 325 | 612 | 827 | 1383 | ||
| Maximum Pressure | mmWG | Máx | 35 | 36 | 32 | 41 | 49 | 70 |
| In. W.G | Min | 1,260″ | 1,299″ | 1,063″ | 1,417″ | 1,457″ | 1,693″ | |
| Máx | 1,378″ | 1,417″ | 1,260″ | 1,614″ | 1,929″ | 2,756″ | ||
| Single-Phase Voltage [V] | 127 / 220 | 220 | ||||||
| Total Power Consumption [W] | 127 V | Min | 66 | – | – | – | ||
| Máx | 88 | – | – | – | ||||
| 220 V | Min | 52,4 | 154,4 | 257,3 | ||||
| Máx | 72,0 | 210,5 | 364,4 | |||||
| Sound Pressure Level [dB]* | Min | 35 | 35 | 31 | 33 | 41 | 41 | |
| Máx | 40 | 40 | 37 | 40 | 46 | 49 | ||
| Ambient Sound Pressure Level – Leq [dBA] ** | Min | 52 | 51 | 48 | 49 | 61 | 62 | |
| Máx | 56 | 57 | 55 | 55 | 67 | 68 | ||
| Speed | – | – | – | – | – | – | ||
| Duct [in] | 4″ | 5″ | 6″ | 8″ | 10″ | 12″ | ||
| Weight | Kg | 3,0 | 3,0 | 3,0 | 3 | 8 | 11 | |
| lbs | 6,6 | 6,6 | 6,6 | 6,6 | 17,6 | 24,3 | ||
*Specifications for 220V/60Hz. Sound pressure level, radiated at 3m in a free field, with ducts at the intake and discharge. 1/3 octave band at 2.5kHz.
** Specifications for 220V/60Hz. Sound pressure level perceived in the environment, radiated at 3m in a free field, with ducts at the intake and discharge.




Models
MAXX 100
Suitable for bathrooms up to 33 m³
MAXX 125
Suitable for bathrooms up to 62 m³
MAXX 150
Suitable for bathrooms up to 99 m³
MAXX 200
Suitable for bathrooms up to 187 m³
MAXX 250
MAXX 315

| MODEL | Dimensional (mm) | |||
|---|---|---|---|---|
| A | B | C | D | |
| Maxx 100 | 96 | 299 | 249 | 218 |
| Moxx 125 | 123 | |||
| Maxx 150 | 148 | |||
| Maxx 200 | 197 | |||
| Maxx 250 | 246 | 383 | 338 | 286 |
| Maxx 315 | 312 | 446 | 410 | 357 |
Download Center
Frequently Asked Questions
The main function of an exhaust fan is to extract gases and vapors from the environment, providing indoor air renewal.
When purchasing your exhaust fan, remember to check the unit’s dimensions and the manufacturer’s installation guidelines.
When we talk about inline exhaust fans that operate along the duct, multiple exhaust fans can be installed in series, that is, one behind the other. However, this will only increase the air pressure, not the airflow rate. To increase the airflow rate, it is necessary to install one exhaust fan next to another, use duplicate ductwork, or use an exhaust fan with a higher airflow rate.
The installation of the exhaust fan must comply with ABNT 14.518/2020, both in terms of performance, dimensions, and construction characteristics.
A good exhaust system should always provide better air quality while meeting the needs of your environment. If you are unsure which product is best for you, you can contact one of our specialists. We have a specialized team with the technical knowledge required to help you make the best choice.
Energy consumption depends greatly on the type of exhaust fan and the environment in which it will be installed.
Sicflux exhaust fan lines offer the advantage of providing air quality and thermal comfort without increasing your energy costs.
Exhaust fans can be installed in any room where the goal is to promote indoor air renewal, offering greater benefits when installed in kitchens and bathrooms, environments that are more susceptible to airborne bacteria. In addition, they are essential for larger environments, such as industrial facilities and commercial establishments.